KTW97 - 200 kg/h
(Hot-Water Heated) - PED, DEMKO approvals and CE marked (Zone 1)

  • Water inlet connection
  • Safety relief valve (gas)
  • Gas temperature probe
  • Water outlet connection
  • Safety relief valve (water)
  • Gas outlet connection
  • Gas inlet connection
  • Water drain plug
Product Description :
Model KTW 97

Heated by recirculated hot water ranging from 40°C to 70°C

Classification : Zone 1

Range : 200 kg/h – subject to conditions in table overleaf.

Operating temperature range : 40°C - 70°C

This safe and reliable hot-water heated LPG vaporizer makes it possible to cover the demands in a medium-sized industrial enterprise where a surplus of hot water or lack of electrical power exists. When installation of a KTW 97 unit is possible and surplus of hot water is available, low installation and running costs will result – refer Operational Conditions Table overleaf.

This unit has been approved according to the highest safety standards allowing it to be placed in Zone 1 (Hazardous Area).Safety distance is not required.

Kosangas LPG recommends that installations be carried out according to local rules and regulations.

Easy to install and maintain :

KTW 97 enables quick installation at low cost. It may utilize either a surplus of hot water from a production/heating process or a separate boiler unit. Kosangas LPG recommends installation of a heat exchanger between the heating source and the vaporizer for safety reasons – to prevent gas from entering into the water heating source e.g. a boiler. No external control box is needed. Maintenance is minimal and all parts are easy to replace. Kosangas LPG recommends the use of anticorrosion/antifreeze (glycol) solution to provide the necessary protection of the water chamber against corrosion and frost.

Technical Description :

KTW 97 is equipped with the following technical features:

  • Solenoid valve (On/Off) controlled by an electronic thermostat.
  • Temperature sensor protects against liquid penetration and overloading.
  • Two safety relief valves protect the pressure vessels against unacceptable pressure increases both in the GAS and the WATER section.
  • Explosion-proof (Zone 1) execution
  • Flameproof control box
  • All electrical components are placed inside a compact control box mounted on the side of the vaporizer
  • Colour : RAL 50-05
Test pressure for GAS section : 32.5 bar (470 psi)
Test pressure for water section : 3.8 bar (56 psi)
Relief valve for GAS section :
Nominal set point 25 bar (360 psi) or 17 bar (250 psi).
Relief valve for WATER section :
Nominal set point 2.5 bar (37 psi)
   
Classification Zone 1:

EEx d m [ia] II A T3,
EN 50014, EN 50018, EN 50028

 

Approvals :
DEMKO (UL subsidiary) and PED (Pressure Equipment Directive) with CE marking.
Scope of supply :
  • Installation and maintenance manuals
  • Pressure and electrical test certificates
  • Transport pallet
  • KPT 97 Remote Monitor Control with cabling
Optional Features :
  • Oil separator for drainage of residues
  • Regulators
  • Boiler unit, pump, heat-exchanger and expansion tank
  • Crating of vaporizer
  • Flanges for gas connection
Norm
Norm
Current
Volume
Voltage
Weight
Gas Section
Inlet / Outlet
Water Section
Inlet / Outlet
Load
Amp.
Water bath
Litre
50/60 Hz
V
Net
kg
BSP 1/2" / BSP 1/2"
BSP 1" / BSP 1"
1.0
60
220/230/240
70

Operational Condition
Variations in Capacities based on inlet temperature
Water Supply
m3/h
Min. outlet
Gas Temperature
Water Temperature
Inlet 45°C - Outlet 40°C
Water Temperature
Inlet 55°C - Outlet 47°C
Water Temperature
Inlet 70°C - Outlet 60°C
2.0
40°C
100 kg/h
170 kg/h
200 kg/h
Energy needed for the Vaporization (Net)
10,000 Kcal/h
17,000 Kcal/h
20,000 Kcal/h
 